Skip to main content

Full text of "IS 3103: Code of Practice for Industrial Ventilation"

See other formats


**************** 


Disclosure  to  Promote  the  Right  To  Information 

Whereas  the  Parliament  of  India  has  set  out  to  provide  a  practical  regime  of  right  to 
information  for  citizens  to  secure  access  to  information  under  the  control  of  public  authorities, 
in  order  to  promote  transparency  and  accountability  in  the  working  of  every  public  authority, 
and  whereas  the  attached  publication  of  the  Bureau  of  Indian  Standards  is  of  particular  interest 
to  the  public,  particularly  disadvantaged  communities  and  those  engaged  in  the  pursuit  of 
education  and  knowledge,  the  attached  public  safety  standard  is  made  available  to  promote  the 
timely  dissemination  of  this  information  in  an  accurate  manner  to  the  public. 


Mazdoor  Kisan  Shakti  Sangathan 
"The  Right  to  Information,  The  Right  to  Live'' 


IS  3103  (1975) :  Code  of  Practice  for  Industrial  Ventilation 
[CED  12:  Functional  Requirements  in  Buildings] 


Jawaharlal  Nehru 
'Step  Out  From  the  Old  to  the  New" 


aj^&vi  iJii^s:y>K^  isb^^ni^seg 


:<>5&i|  mT'5K^5?::5:^>^i»l 


K^^^iXSVCd^ 


Satyanarayan  Gangaram  Pitroda 
Invent  a  New  India  Using  Knowledge 


Bhartrhari — Nitisatakam 
''Knowledge  is  such  a  treasure  which  cannot  be  stolen" 


^'^^^r 


k 


BLANK  PAGE 


^*-^^^ 


PROTECTED  BY  COPYRIGHT 


Indian  Standard 


IS:  3103 -1975 

( Reaffirmed  2004 ) 


CODE  OF  PRACTICE  FOR 
INDUSTRIAL  VENTILATION 

( First  Revision  ) 


Thiid  Reprint  MAY  1993 


UDC     628.83:725.41 


@  Copyright  W16 

BUREAU    OF    INDIAN    STANDARDS 

MANAK  BHAVAN,  9  BAHADUR  SHAH  ZAFAR  MARG 
NEW  DELHI  110002 

Gr5  May  1976 


15:3103*1975 

Indian  Standard 

CODE  OF  PRACTICE  FOR 
INDUSTRIAL  VENTILATION 


( First  Revision  ) 


Functional  Requirements  in  Buildings  Sectional  Committee,  BDC  12 
Chairman  Representing 

Lt  -Gen  B.  N.  Das*  Ministry  of  Defence 

Members 

Additional  Dibector  Standards  Ministry  of  Railways    ' 
(  Architecture  ) 

Joint  Director  Standards 
(  Architect  )  (  Alternate  ) 
Director  Directorate  GeHcral  of  Observatories,  New  Ejrlhi  ^ 

Director  (  Architecture  )  Central  Public  Works  Department 

ShRIMATi  E.  S.  Ghuman  Indian  Institute  of  Architects,  Bombay 

ShriJ.  M.  Benjamin    [Alternate) 
Shri  R.  G.  Gokkale  In  personal  capacity  (  Nirman  Bkavan,  Ntw  Delhi  ) 

Shbi  J.  G.  Kapur  Danfoss  (  India  )  Ltd,  New  Delhi 

Shri  B.  D.  Kshirsagar  Ministry  of  Defence 

Shbi  L.  R.  Lalla  (  Alternate  )     " 
Shri  G.  C.  Mathur  National  Buildings  Organization 

Shri  M.  M.  Mistry  (  Alternate  ) 
Db  V.  Narasimhak  Central  Building  Research  Institutc(  CSIR  },  Roorkee 

Shbi  M.  R.  Sharma   (  Alternate  ) 
Shbi  J.  R.  Ovalekab  National  Safety  Council,  Bombay 

Shri  N.  Raghavan  (  Alienate  ) 
Shbi  M.  M.  Pande  Voltas  Ltd,  Bombay 

Shbi  R.  N.  Pawar  Directorate  General  of  Health  Services.  New  Delhi 

ShriS.  Purushothama  Ministry   of  Labour,    Employment  &  Rehabilitation, 

New  Delhi 
Prof  Rattan  Kumar  University  of  Roorkee  *       * 

Shri  S.  SuBBA  Rao  All    India    Institute   of   Hygiene    &    Public   Health, 

Calcutta 

Shbi  A.  V.  Rao  {  Alternate  ) 
Shri  Saved  S.  Shafi  Institute  of  Town  Planners,  Nt-w  Delhi  - 

Shri  D.  P.  Sharma  (  Alternate ) 


*Also  represents  the  Institution  of  Engineers  (  India  ). 

(  Continued  om  pa0e2  ) 


^  Copyright   1976 

BUREAU    OF    INDIAN    STANDARDS 

This  publication  is  protected  under  the  Indian  Copyright' Act  [  XtV  uf  1957 /and 
reproduciion  in  whole  or  in  part  by  any  means  except  with  written  permission  ot  the 
publisher  shall   be  deemed  to  be  an  infringement  of  copyright  under  the  tafd  Act. 

»    ■  ' 


IS:  3103 -1975 

(  Continued  from  page  1  ) 

Members 
Shei  R.  L.  Subi 

Shbi  D,  Ajitha  Simha, 
Director  (  Civ  Engg  ) 


Representing 

Suri    &     Suri     Consulting     Acoustical     Engineers, 

New  Delhi 
Director  General,  ISI  (  Ex-offieio  Member  ) 


Secretary 

ShrI  V.    KAXYANAStTNDARAM 

Assistant  Director  (  Civ  Engg  ),  ISI 


Forced  Ventilation  ( Industrial )  Subcommittee,  BDC  12  : 8 


Convener 

Shei  J.  C,  Kapur 

Members 

Shri  K.  N.  Bhar 
Shri  a.  Datta 

Surg  Cdr  M.  S.  Malhotra 
Shri  J .  G  .  M anqi«a)7i 

Shri  H.  V.  Sharma  (  Alternate 
Shri  Naunihal  Singh 

Shri  Shiv  Nath  (  Alternate  ) 
Shri  S.  Pitrushothama 
Shri  S.  Subba  Rao 

Shri  A.  V.  Rao  (  Alternate  ) 
Shri  N.  Sbshadri 

Shri  K.  Sitbrahamanyam 


Danfoss  ( India  )  Limited,  New  Delhi 


Central  Public  Works  Department 

Keymcr,    Bagshawc    &    Co     ( India  )    Private  Ltd, 

Calcutta 
Ministry  of  Defence 
Air. Conditioning  Corporation  Ltd,  Calcutta 

National  Physical  Laboratory  (  GSIR  ),  New  Delhi 

Miniitry  of  Labour  Employment  &  Rehabilitation 
All    India  Institute  of  Hygiene  &   Public    Health, 
Calcutta 

India  Mcteorcrfogical  Department  (The  Observatory), 

New  Delhi 
Ahmadabad  Textile  Industry's  Research   Association, 

Ahmadabad 


18:3103-1975 

Indian  Standard 

CODE  OF  PRACTICE  FOR 
INDUSTRIAL  VENTILATION 

{ First  Revision  ) 

0.     FOREWORD 

0.1  This  Indian  Standard  (  First  Revision  )  was  adopted  by  the  Indian 
Standards  Institution  on  31  December  1975,  after  the  draft  finalized  by  the 
Functional  Requirements  in  Buildings  Sectional  Committee  had  been 
approved  by  the  Civil  Engineering  Division  Council, 

0.2  Due  consideration  should  be  given  to  the  ventilation  requirements  in 
designing  factories  and  industrial  buildings.  Provision  for  ventilation 
becomes  necessary  for  dilution  of  inside  air  to  prevent  vitiation  by  causes, 
such  as  body  odours,  to  remove  contaminants  in  air  released  during 
manufacturing  processes  and  to  maintain  satisfactory  thermal  enviroments. 
The  application  of  ventilation  should  be  considered  with  other  measures  to 
control  heat  given  off  during  industrial  processes.  Ventilation  by  natural 
meahs  may  not  be  sufficient  in  certain  industries  to  provide  such  thermal 
environments  as  will  assist  the  maintenance  of  heat  balance  of  the  body 
and  to  prevent  acute  discomfort  and  injury  to  the  health  of  the  workers. 
In  such  cases  mechanical  ventilation  and  cooling  systems,  where  neces- 
sary, may  be  employed  to  achieve  satisfactory  results.  Sortie  principles  of 
industrial  ventilation  are  dealt  with  in  this  code  in  order  to  give  guidance 
to  those  concerned  in  this  field.  In  the  preparatioti  of  this  code,  the 
requirements  of  the  Factories  Act  and  Rules  thereunder  have  been  taken 
into  consideration. 

0.3  This  standard  covers  ventilation  of  industrial  buildings  only  and  was 
first  published  in  1965.  The  present  revision  waS  taken  tip  with  a  view  to 
incorporate  necessary  provisions  regarding  control  of  heat  hazards  due  to 
various  processes  in  the  industry.  Some  of  the  significant  changes  made 
are  given  in  0.3.1. 

0.3.1  In  this  code  certain  new  definitions  have  been  a^ded.  The  range 
of  recommended  capture  velocities  and  the  provisions  for  orientation  of 
buildings  have  been  included.  The  design  considerations  for  ventilation, 
provisions  for  mechanical  ventilation  have  been  modificdr  The  require- 
ments for  ventilation  of  buildings,  natural  ventilation  and  positive  ventila- 
tion have  also  been  modified. 


1$  13103-1975 

0.4.  The  current  practice  in  this  country  regarding  the  threshold  limit 
values  for  contaminants  (  see  2*21  and  4.5.1  )  is  to  refer  to  the  latest  pub- 
lication of  the  American  conference  of  Governmental  Industrial  Hygienists. 

0.5  For  the  purpose  of  deciding  whether  a  particular  requirement  of^is 
standard  is  complied  with,  the  final  value,  observed  or  calculated,  express- 
ing, the  result  of  a  tester  analysis,  shall  be  rounded  off  in  accordance  with 
IS  :  2-1960*.  The  number  of^ignificant  places  retained  in  the  rounded  off 
value  should  be  the  same  as  that  of  the  specified  value  in  this  standard. 


1.  SCOPE 

1.1  This  standard  covers  certain  basic  requirements  regarding  safe  design, 
installation,  operation,  te^ne  and  maintenance  of  ventilating  systems  with 
respect  to  general  ventilation  and  wherever  appropriate  dilution  ventila- 
tion for  industrial  process.  This  standard  also  briefly  describes  measures 
to  reduce  the  heat  hazards  due  to  industrial  processes. 

2.  TERMINOLOGY 

2.0  For  the  purpose  of  this  standard,  the  following  definitions  shall  apply. 

2.1  Air  Change  per  Hour  —  The  volume  of  outside  air  allowed  into  a 
room  in  one  hour  compared  with  the  volume  of  the  room. 

2-2  Aarial  Flow  Fan  —  A  fan  having  a  casing  in  which  the  air  enters  and 
leaves  the  inipellcr  in  a  direction  substantially  parallel  to  its  axis. 

2  J  Capture  Velocity  —  Air  velocity  at  any  point  in  front  of  the  exhaust 
hood  necessary  to  overcome  opposing  air  currents  and  to  capture  the 
contanUnated  air  at  that  point  by  causing  it  to  flow  into  the  exhaust  hood. 

2.4  Centrifugal  Fan  —  A  fan  in  which  the  air  leaves  the  impeller  in  a 
direction  substantially  at  right  angles  to  its  axis. 

23  Contandboauts^^  Dusts,  fumes,  gases,  mists,  vapours  and  such  other 
substances  present  in  air  are  likely  to  be  injurious  or  offensive  to  the 
occupants. 

2.6  PUution  Ventilatioo  —  Supply  of  outside  air  to  reduce  the  air-borne 
concientration  of  contaminants  in  the  building. 

2.7  Dry  Bidb  Temperature  —  The  temperature  of  the  air  read  on  a 
thermometer,  placed  in  such  a  way  as  to  avoid  errors  due  to  radiation. 

*Rulcs  for  rounding  off  numerical  values  (  revised). 

4 


tS  :  3103  -  1975 

2*8  Exhaust  of  Air — Removal  of  air  fromr  a  building  and  its  disposal 
outside  by  means  of  mechanical  device,  such  as  a  fan. 

2.9  General  Ventilation  —  Supply  of  outside  air  either  by  positive 
ventilation  or  by  infiltration  into  the  building. 

2.10  Humidification  —  The  process  whereby  the  absolute  humidity  of 
the  air  in  a  building  is  maintained  at  a  higher  level  than  that  of  outside  air 
or  at  a  level  higher  than  that  which  would  prevail  naturally. 

2-11  Humidity  Absolute  —  The  weight  of  water  vapour  per  unit  volume. 

2.12  Humidity  Relative  —  The  ratio  of  the  actual  to  the  partial  pressure 
of  the  water  vapour  at  the  same  temperature. 

2.13  Local  Exhaust  Ventilation  —  Ventilation  effected  by  exaust  of  air 
through  an  exhaust  appliance,  such  as  hood  with  or  without  fan  located  as 
closely  as  possible  to  the  point  at  which  contaminants  are  released  so  as  to 
capture  effectively  the  contaminants  and  convey  them  through  ducts  to  a 
safe  point  of  dispharge. 

2.14  Make  Up  Air  —  Outside  air  supplied  into  a  building  to  replace  the 
air  removed. 

2.15  Mechanical  Ventilation  —  Supply  of  outside  air  either  by  positive 
ventilation  or  by  infiltration  by  reduction  of  pressure  inside  due  to  exhaust 
of  air,  or  by  a  combination  of  positive  ventilation  and  exhaust  of  air. 

2.16  Natural  Ventilation  —  Supply  of  outside  air  into  a  building  through 
window  or  other  openings  due  to  wind  outside  and  convection  effects 
arising  from  temperature  or  vapour  pressure  differences  ( or  both )  between 
inside  and  outside  of  the  building. 

2.17  Positive  Ventilation  —  The  supply  of  outside  air  by  means  of  a 
mechanical  device,  such  as  a  fan. 

2,1'8  Propeller  Type  Fan  — A  fan  in  which  the  air  leaves  the  impeller  in 
a  direction  substantially  parallel  to  its  axis  designed  to  operate  normally 
under  free  inlet  and  outlet  conditions. 

2.19  Spray-head  Systems  —  A  system  of  atomizing  water  so  as  to 
introduce  the  moisture  directly  into  a  building. 

2.20  Temperature  Rise  —  Difference  of  exit  temperature  and  the 
temperature  of  air  at  the  inlet  openings*^ 

2.21  Threshold  Limit  Values  (TLV)  —  Refers  to  air-borne   concentra- 
tion of  contaminant  and  represent  conditions,  under  which  it  is  believed 
that  nearly  all  occupants  may  be  repeatedly  exposed,  day  after  day,  with-  , 
out  adverse  effect. 


IS :  3103  - 1975 

2.22  Ventilation  —  Supply  of  outside  air  into,  or  the  removal  of  inside 
air  from  an  enclosed  space. 

2.23  Wet  Bulb  Ten^erature  —  The  steady  temperature  finally  given  by 
a  thermometer  having  its  bulb  covered  with  gauze  or  muslin  moistened  with 
distilled  water  and  placed  in  an  air  stream  of  not  less  than  4*5  m/s, 

3.  ORIENTATION  OF  BUILDINGS 

3.1  Solar  Load  Factors  —  In  the  tropics  orientation  for  minimum  solar 
load  during  summer  should  be  the  main  criterion.  Wherever  appropriate, 
orientation  to  avoid  the  solar  heat  during  summer  and  to  take  the  desir- 
able'heat  during  winter  should  be  preferred. 

3.1.1  Wherever  possible  suitable  sun-breakers  have  to  be  provided  to  cut 
off  the  incursion  of  direct  sunlight  to  prevent  heat  radiation  and  to  avoid 
glare. 

4.  DESIGN  CONSIDERATION 

4.1  General  —  Ventilation  is  required  to  supply  fresh  air  for  respiration, 
to  dilute  inside  air  to  prevent  vitiation  by  body  odours,  to  remove  any 
contaminants  in  air  and  to  provide  such  thermal  environments  as  will 
assist  in  the  maintenance  of  heat  balance  of  the  body  in  order  to  prevent 
discomfort  and  injury  to  health  of  the  occupants. 

4.1.1  Respiration  —  Supply  of  fresh  air  to  provide  oxygen  for  the  human 
body  forXelimination  of  waste  products  and  to  maintain  carbon  dioxide 
concentration  in  the  air  within  safe  limits  rarely  calls  for  special  attention 
as  enough  outside  air  for  this  purpose  normally  enters  the  areas  of  occu- 
pancy through  crevices  and  other  openings. 

4.1.2  Vitiation  by  Body  Odours  —  Where  no  contaminants  are  to  be 
removed  from  air,  the  amount  of  fresh  air  required  for  dilution  of  inside 
air  to  prevent  vitiation  by  body  odours,  depends  on  the  air  space  available 
per  person  and  the  degree  of  physical  activity;  the  amount  of  air  decreases 
as  the  air  space  per  person  increases,  and  it  may  vary  from  20  m*  to  30  m' 
per  person  per  hour.  In  rooms  occupied  by  only  a  small  number  of  person 
such  an  air  change  will  automatically  be  attained  in  cool  weather  by 
normal  leakage  around  windows  and  other  openings  and  this  may  easily 
be  secured  in  warm  weather  by  keeping  the  openings  open. 

4*1.2.1  Recommended  values  for  air  changes  —  No  standards  have  been 
laid  down  under  the  Factories  Act  (1948),  as  regards  the  aniount  of  fresh 
air  required  per  worker  or  the  number  of  air  changes  per  hour.  Section 
16  relating  to  overcrowding  requires  that  at  least  14  m'  to  16  m*  of  space 
shall  be  provided  for  every  worker  and  for  the  purpose  of  that  section  no 
account  shall  be  taken  of  spaces  in  a  work  room  which  is  more  than  4*25  m 
above  the  floor  level. 


lS:dl03-1975 

4.1.2.2  The  minimum  fresh  air  required  in  a  work  room  where  there 
are  no  contaminants  to  be  removed  from  air,  shall  be  such  as  to  effect  at 
least  three  air  changes  per  hour, 

4.1.3  Heat  Balance  of  Body  —  Specially  in  hot  weather,  when  thermal 
environment  inside  the  room  is  worsened  by  heat  given  off  by  machinery, 
occupants  and  other  sources,  the  prime  need  for  ventilation  is  to  provide 
such  thermal  environment  as  will  assist  the  maintenance  of  heat  balance  of 
the  body  in  order  to  prevent  discomfort  and  injury  to  health.  Excess  of 
heat  from  a  hot  environment  has  to  be  offset  to  maintain  normal  body 
temperature  (  37°C  ).  Heat  exchange  of  the  human  body  with  respect  to 
surroundings  is  determined  by  temperature  and  humidity  gradient  between 
the  skin  and  surroundings,  and  therefore  depends  on  air  temperature  (  dry 
bulb  temperature  ),  relative  humidity  ( or  wet  bulb  temperature  ),  radia- 
tion from  the  surroundings  and  air  movement.  The  volume  of  outside 
air  to  be  calculated  through  the  room  is,  therefore,  governed  by  the 
physical  considerations  of  controlling  the  temperature,  air  distribution  or 
air  movement. 

4*1«3.1  Proper  air  movement  and  fresh  2iir  supply  will  reduce  heat 
stress  by  dissipating  heat  from  body  by  evaporation  of  the  sweat  particu- 
larly when  relative  humidity  is  high  and  the  air  temperature  is  below  or 
near  body  temperature.  Aar  movement  and  distribution  may,  however, 
be  achieved  by  recirculation  of  the  inside  and/or  outside  air. 

4.1.3.2  In  industrial  buildings  where  workers  wearing  light  clothing 
are  expected  to  do  work  of  moderate  severity  with  the  energy  expenditure 
in  the  range  235  to  330  kcal/h,  the  maximum  wet  bulb  temperature  shall 
not  exceed  29°C  and  adequate  air  movement  subject  to  a  minimum  of  air 
velocity  of  30  m/min  shall  be  provided;  and  in  relation  to  the  dry  bulb 
temperature,  the  wet  bulb  temperature  of  air  in  the  work  room  as  far  as 
practicable,  shall  not  exceed  to  that  given  in  Table  1 . 

4.2  Control  of  Heat — Although  it  is  recognised  that  ventilation  is  one 
of  the  most  effective  methods  of  controlling  the  thermal  conditions  in 
factories,  in  many  situations,  the  application  of  ventilation  should  be 
preceded  by  and  considered  along  with  some  of  the  following  other  methods 
of  control.  This  would  facilitate  better  design  of  ventilation  systems  and 
also  reduce  their  cost. 

4.2.1  Isolation  —  Sometimes  it  is  possible  to  locate  heat  producing 
equipment,  such  as  furnaces  in  such  a  position  as  would  expose  only  a 
small  number  of  workers  to  hot  environments.  As  far  as  practicable 
such  sources  of  heat  in  factories  should  be  isolated. 

4.2«1«1  In  situations  where  relatively  few  people  are  exposed  to  severe 
heat  stress  and  their  activities  are  confined  to  limited  areas  as  in  the  case 
of  rolling  mill  operators  and  crane  operators,  it  may  be  possible  to  enclose 
the  work  areas  and  supply  conditioned  air  to  such  enclosures. 


IS :  3103  -  1975 


TABLE   1     MAXIMUM  PERMISSIBLE  WET  BULB  TEMPERATURES 
FOR  GIVEN  DRY  BULB  TEMPERATURE 


(  Clauses ^.U3.2,  4.3.3  and 43 A  ) 


Day  Bulb 
Tbmpebatuke,  °C 

Maximum  Wet  Bulb 
Tbmpkratukb,  **C 

30 

29-0 

35 

28-5 

40 

280 

45 

27-5 

50 

27-0 

Note  1 — The  limits  indicated  in  the  table  are  based  on  the  upper  safe  limits 
recommended  in  the  report  Thermal  Stress  on  Textile  Industry  (  Report  No.  1 7  ) 
issued  by  the  Chief  Adviser  Factories,  Government  of  India,  Ministry  of  Labour  and 
Employment,  New  Delhi;  these  are  limits  beyond  which  the  industry  should  not  allow 
the  thermal  conditions  to  go  for  more  than  one  hour  continuously.  The  limits  arc 
based  on  a  series  of  studies  conducted  on  Indian  subjects  in  a  psychrometric  chamber 
and  on  other  data  on  heat  casualties  in  earlier  studies  conducted  in  Kolar  Gold  Fields 
and  elsewhere. 

Note  2  —  Figures  given  in  the  table  arc  not  intended  to  convey  that  human  eflSciency 
at  50*0  will  remain  the  same  as  at  30*'C  provided  appropriate  wet  bulb  temperatures 
are  maintained.  Efficiency  decreases  with  rise  in  the  dry  bulb  temperature  for  a 
given  wet  bulb  temperatures  attained  and  efforts  should  be  made  to  bring  down  the 
dry  bulb  temperatures  as  Well,  as  much  as  possible.  Long  exposures  to  temperature 
of  50*C  dry  bulb/27*C  wet  bulb  may  prove  dangerous. 

Note  3 — ■Refrigeration  or  other  naethod  of  cooling  is  reconmiended  in  all  cases 
where  conditions  would  be  worse  than  those  shown  in  this  table. 

4*2»2  Ihsulatian  —  A  considerable  portion  of  heat  in  many  factories  is 
due  to  the  solar  radiation  falling  on  the  roof  surfaces,  which  in  turn 
radiate  heat  inside  the  factories.  In  such  situations,  insulation  of  the  roof 
or  providing  a  false  ceiling  or  double  roofing  would  be  very  effective  in 
controlling  heat.  Some  reduction  can  also  be  achieved  by  painting  the 
roof  in  heat  reflective  shades. 

Hot  surfaces  of  equipments,  such  as  pipes,  vessels,  etc  in  the  factory 
should  also  be  insulated  to  reduce  their  surface  temperature. 

4.2«3  Substitution  —  Sometimes,  it  is  possible  to  substitute  a  hot  process 
by  a  method  that  involves  application  of  localised  or  more  efficiently 
controlled  method  of  heating.  Examples  include  induction  hardening 
instead  of  conventional  heat  treatment,  cold  rivetting  or  spot  welding 
instead  of  hot  rivetting,  etc. 

4«2*4  Radiant  Shielding — Hot  surfaces,  such  as  layers  of  molten  metal  ema- 
nate radiant  heat  which  can  best  be  controlled  by  placing  a  shield  having  a 

8 


IS:  3103    1975 

lighly  reflecting  surface  between  the  source  of  heat  and  the  worker  so 
hat  a  major  portion  of  the  heat  falling  on  the  shield  is  reflected  back  to 
he  source.  Surfaces,  ^uch  as,  of  tin  and  aluminium  have  been  used  as 
materials  for  shields.  The  efficiency  of  the  shield  does  not  depend  on  its 
thickness  but  on  the  reflectivity  and  emissivity  of  its  surface.  Care  should 
be  taken  to  see  that  the  shield  is  not  heated  up  by  conduction  and  for  this 
purpose  adequate  provision  should  be  made  for  the  free  flow  upwards  of 
the  heated  air  between  the  hot  surface  and  the  shield  by  leaving  the 
necessary  air  space  and  providing  opening  at  the  top  and  the  bottom  of 
the  si^es. 

4.3  Ventilation  of  Buildings  —  In  the  case  of  an  industrial  building 
having  a  significant  internal  heat  load  due  to  manufacturing  processes,  the 
following  items  may  be  considered  when  designing  for  the  maximum 
possible  control  of  thermal  environment: 

a)  Orientation  of  the  building  with  respect  to  the  direction  of  the 
prevailing  winds  and  of  the  path  of  the  sun  in  the  sky  and  to  the 
location  of  adjoining  buildings. 

b)  Configuration  of  the  building  and  the  manufacturing  processes 
in  it, 

c)  Proper  inlets  (windows  and  other  openings)  and  their  location 
with  respect  to  outlet  openings. 

d)  Mechanical  ventilation  including  selection  and  disposition  of  fans, 
inlet  grilles  and  arrangement  of  ducts. 

In  the  case  of  industrial  buildings  wider  than  30  m,  the  ventilation 
may  be  augmented  by  roof  ventilation. 

4*3.1  The  volume  of  air  required  shall  be  calculated  by  u§ing  both  the 
sensible  heat  or  latent  heat  as  the  basis.  The  lai^cr  of  the  two  figures 
obtained  should  be  used  in  actual  practice. 

4«3»1*1  Volume  of  air  required  for  removing  sensible  heat  when  the 
amount  of  sensible  heat  given  off  by  different  sources  namely  the  sun,  the 
manufacturing  processes  machinery,  occupants  and  other  sources  is  known 
and  a  suitable  value  for  the  allowable  tenaperature  rise  is  assumed,  the 
volume  of  outside  air  to  be  provided  for  removing  the  sensible  heat  m.ay 
be  calculated  from: 

n  3-462  X  K, 

where 

0,1  ==  quantity  of  air  in  m*/h, 
JTg  ==  sensible  heat  gained  in  kcal/h,  and 
t     =r  allowable  tem.perature  rise  in  °& 


18:314)3-1975 

4.3.1.2  Temperature  rise  refers  mainly  to  the  diflference  between  the 
air  temperature^  at  the  outside  and  at  the  inlet  openings.  As  very  little 
data  exist  on  allowable  temperature-rise  values  for  supply  of  outside  air 
in  summer  months,  the  values  given  in  Table  2  related  to  industrial 
buildings  may  be  used  for  general  guidance. 

TABLE    2     ALLOWABLE  TEMPERATURE-RISE  VALUES 

{  Clauses  4.3.1.2  anrf 4.3.4  ) 

Height  of  Outlet  Tkmpkrature  Rise 

Openings 

6  3  to    4-5 

9  4-5  to    6-5 

12  fi-5to  11 

Note  I  — The  conditions  arc  limited  to  light  or  medium  heavy  manufacturing  pro- 
cesses, freedom  from  radiant  heat  and  inlet  openings  not  more  than  3  to  4*5  m  above 
floor  level. 

Note  2  —  At  the  working  zone  between  floor  level  and  1*5  m  above  floor  levels  the 
recommended  maximutn  allowable  temperature  rbe  for  air  is  2  to  3**C  above  the  air 
temperature  at  the  inlet  openings. 

4.3.1.3  Volume  of  aif  required  for  removing  latent  heat  —  If  the  latent 
heat  gained  from  the  manufacturing  processes  and  occupants  is  also 
known  and  a  suitable  value  for  the  allowable  rise  in  the  vapour  pressure 
is  assumed: 

4  800  X  ki 
0.2  = -^ 

where 

0,2  =  quantity  of  air  in  m'/h, 

^1    =  latent  heat  gained  in  k  cal/h,  and 

h     —  allowable  vapour  pressure  difference  in  mm  of  mercury. 

Note  — •  In  majority  of  the  cases  the  sensible  heat  gain  will  far  exceed  the  latent 
heat  gain  so  that  the  amount  of  outside  air  to  be  drawn  by  ventilating  equipment  can 
be  calculated  in  moit  cases  on  the  basis  of  the  equation  given  in  4.3.1.1. 

4.3.1.4  Ventilation  is  also  expressed  as  m^h/m*  of  floor  area.  This 
relationship  fails  to  evaluate  the  actual  heat  relief  provided  by  a  ventila- 
tion system,  but  it  does  give  a  relationship  which  is  independent  of  build- 
ing  height.  This  is  a  more  rational  approach  because,  with  the  same 
internal  load,  the  same  amount  of  ventilation  air,  properly  applied  to  the 

\0 


IS :  3103  - 1975 

work  zone  with  adequate  velocity,  will  provide  the  desired  heat  relief 
quite  independently  of  the  ceiling  height  of  the  space,  with  few  exceptions. 
Ventilation  rates  of  30  to  60  m^h/m'  have  been  found  to  give  good  results 
in  many  plants. 

4.3.2  Natural   Ventilation — The   rate  of  ventilation    by  natural   means 
through  windows  or  other  openings  depends  on: 

a)  direction  and  velocity  of  wind  outside  and  size  and  disposition  of 
opening  (wind  action),  and 

b)  convection  effects  arising  from  temperature  or  vapour  pressure 
difference  (or  both)  between  inside  and  outside  the  room  and  the 
difference  of  height  between  the  outlet  and  inlet  openings  (stack 
effect). 

4.3.2.1  By  wind  action 

a)  Inlet  openings  in  the  building  should  be  well  distributed  and 
should  be  located  on  the  windward  side  at  a  low  level  and  outlet 
openings  should  be  located  on  the  leeward  side  near  the  top  so 
that  incoming  air  stream  is  passed  over  the  occupants.  Inlet  and 
outlet  openings  at  high  level  may  only  clear  the  top  air  without 
producing  air  movement  at  the  level  of  occupancy.  When  outlets 
serve  as  inlets,  they  shall  be  located  at  the  same  level. 

b)  Inlet  openings  should  not,  as  far  as  possible,  be  obstructed  by 
adjoining  buildings,  trees,  signboards  or  other  obstructions  or  by 
inside  partitions  in  the  path  of  air  flow. 

c)  Greatest  flow  per  unit  area  of  openings  is  obtained  by  using  inlet 
and  outlet  openings  of  nearly  equal  areas. 

d)  Where  the  stream  of  wind  is  quite  constant  and  dependable  the 
openings  may  be  readily  arranged  to  take  full  advantage  of  the 
wind.  Where  the  wind  direction  is  quite  variable,  the  openings 
shall  be  arranged  so  that  as  fai^,as  possible  there  is  approximately 
equal  areas  on  all  sides  and  the  openings  be  located  at  the  same 
levels.  Thus  no  matter  what  the  wind  direction  is,  there  are 
always  some  openings  directly  exposed  to  wind  pressure  and  others 
to  air  s,uction  and  effective  movement  through  buildings  is  assured. 

4.3.2*2  By  stack  effect  —  Natural  ventilation  by  stack  effect  occurs 
when  air  inside  a  building  is  at  a  different  temperature  than  air  outside. 
Thus  in  heated  buildings  or  in  buildings  wherein  hot  processes  are  carried 
on  and  in  ordinary  buildings  during  summer  nights  and  during  premon- 
soon  periods,  the  inside  temperature  is  higher  than  that  of  outside,  cool 
outside  air  will  tend  to  enter  through  openings  at  low  level  and  warm  air 
will  tend  to  leave  through  openings  at  high  level.  It  would,  therefore,  be 
advantageous  to  provide  ventilators  as  close  to  ceilings  as  possible.  Venti- 
lators 'can  also  be  provided  in  roofs  as,  for*  example,  cowl,  vcntipipe, 
covered  roof  and  ridge  vent. 

11 


rS  :  3103  -  1975 

4.3,3  Mechanical  Ventilation,  General  —  Where  adequate  air  changes 
specified  in  recommended  values  for  air  changes  or  for  providing  thermal 
environment  within  the  limits  specified  in  Table  1  whichever  is  higher, 
cannot  be  obtained  by  natural  ventilation,  mechanical  ventilation  either 
by  exhaust  of  air  or  by  positive  ventilation  or  combination  of  the  two 
shall  be  provided,  and  in  case  of  positive  ventilation  where  necessary,  air 
before  being  brought  into  the  area  of  occupancy,  may  be  cooled  by 
evaporative  cooling  or  by  air-conditioning. 

4.3.3.1  Exhaust  of  air — Exhaust  fans  are  provided  in  walls  on  one 
side  of  the  building  or  in  the  attic  and  roofs  to  draw  large  volumes  of  air 
through  the  building.  These  fans  are  usually  of  propeller  type  since  they 
operate  against  little  or  no  resistance.  It  is  important  that  windows  and 
other  openings  near  the  fans  are  kept  closed  as  otherwise  the  fans  would 
draw  outside  air  from  these  openings  and  cause  what  is  termed  as  ^short- 
circuiting'.  Adequate  inlet  openings  shall  be  provided  on  opposite  side 
of  the  building  so  as  to  limit  inlet  velocities.  When  fans  are  centrally 
located  on  an  attic  or  other  unused  space  and  arranged  to  draw  propor- 
tionately from  several  work  areas  or  from  exhaust  appliances  with  duct 
work,  these  are  predominantly  centrifugal  type  or  sometimes  axial  types 
so  as  to  overcome  the  resistance  from  duct  work. 

4*3*3«2  Positive  ventilation  —  Positive  ventilation  is  provided  by 
centrally  located  supply  fans  which  are  usually  of  centrifugal  type  having 
a  wide  range  of  capacities  and  quiet  operation.  Considerable  advantage 
may  be  acliieved  by  incorporating  the  ducts  into  the  building  structure 
and  by  having  the  interior  surfaces  carefully  finished  to  render  them 
smooth  and  air-tight  and  treated  to  prevent  the  possibility  of  dust  being 
scoured  from  the  walls  by  the  passing  air.  Unit  ventilators  may  be  pro- 
vided for  individual  rooms  and  may  be  placed  against  outside  wall  near 
the  central  line  of  the  room.  Both  central  system  and  unit  ventilators 
could  be  equipped  to  provide,  besides  the  function  of  ventilating,  cooling 
by  evaporative  cooling  coils.  Typical  installations  are  equipped  with 
systems  of  controls  that  permits  ventilating  and  cooling  effect  to  be  varied, 
while  the  fans  are  operating  continuously,  in  accordance  with  the  room 
requirements. 

4.3.3.3  Combined  systems  —  The  combined  systems  with  positive 
ventilation  and  with  exhaust  of  air  have  the  advantage  of  providing  better 
control  conditions  and  better  distribution  of  air  over  the  entire  area  of 
occupancy  particularly  in  wider  buildings.  By  supplying  proper  volumes 
of  air  at  suitable  velocities  at  the  required  areas  through  duct  work  and 
by  extracting  the  air  in  the  return  ducts  and  recirculating  this  air  after 
properly  mixing  it  with  cool  fresh  air,  completely  satisfactory  ventilation 
is  obtained.  In  a  combined  system  it  is  preferable  to  provide  slight 
excess  of  exhaust  if  there  are  adjoining  occupied  spaces  and  a  slight  excess 
of  supply  if  there  are  no  such  spaces.  Unit  exhausters  can  also  be  used 
to  match  unit  ventilators'  exteriors  and  located  along  the  outside  wall. 

12 


18:3103-1975 

4*3«4  Evaporative  Cooling  —  In  regions  where  high  day-time  temperatures 
prevail  with  reasonably  low  humidities,  evaporative  cooling  may  be  em- 
ployed effectively  to  lower  the  temperature  of  the  air  to  near  the  wet  bulb 
temperature  and  produce  an  air  supply  cool  enough  to  take  care  of  the 
indoor  sensible  heat  loads  without  exceeding  the  upper  safe  limits  given  in 
Table  1  'or  the  temperature  rise  values  at  area  of  occupancy  given  in  Note  2 
in  Table  2.  By  positive  ventilation  this  air  may  be  supplied  to  produce 
cooler  environments  with  lower  air  volume  than  would  be  required 
under  4.3.1.1*  The  amount  of  air  required  as  greater  temperature  rise  than 
given  under  Table  2  may  be  tolerated.  Although  the  relative  humidity 
of  supply  air  will  be  increased  but  due  to  the  large  sensible  heat  loads  the 
resultant  relative  humidity  of  the  air  will  be.  sufficiently  lowered  after 
mixing  with  the  inside  air  to  produce  body  cooling. 

4.3.4.1  Evaporative  cooling  with  positive  ventilation  using  a  central 
plant  consisting  of  a  water  spray  chamber  and  a  fan  to  supply  outside  air 
into  the  work  room  through  a  distribution  duct  is  far  preferable  to  spray 
head  system  which  only  humidifies  the'air,  the  cooling  capacity  of  the  air 
will  be  very  little  improved;  and  none  of  the  air  which  absorbs  the  heat 
given  off  by  machinery,  manufacturing  processes  and  occupants,  is 
removed  from  the  building  under  these  conditions, 

4.3.4.2  Evaporative  cooling  is  generally  used  where  humidification .  is 
necessary  to  meet  the  requirements  of  manufacturing  processes  in  factories, 
as  for  instance,  in  a  cotton  mill  to  keep  the  textile  fibres  pliable  and 
strong  in  a  rubber  factory  to  prevent  static  electricity  in  processes  using 
volatile  and  inflammable  solvents  or  in  printing  and  lithographic  works  to 
maintain  accurately  the  size  of  the  paper  and  other  materials. 

4.3.4.3  Where  humidification  or  dehumidification  is  necessary  to' meet 
the  requirements  of  manufacturing  processes,  the  requirements  shall  be 
ascertained  from  the  clients.  In  respect  of  cotton  spinning  and  weaving 
factories,  attention  is  drawn  to  the  requirements  regarding  temperatures 
and  humidities  under  relevant  rules  framed  by  the  State  Government 
under  Section  15  of  the  Factories  Act  (1948). 

4.3.5  Air-Conditioning  —  Where  the  desired  temperatures  and  humidities 
cannot  be  obtained  by  mere  ventilation,  air  conditioning  may  be  resorted 
to  {see  IS  :  659-1964*  and  IS  :  660-1963t). 

4.3.5*1  When  refrigeration  is  employed  to  obtain  desired  temperature 
inside  a  work  room  it  may  be  necessary  to  circulate  more  air  than  that 
required  for  ventilation  purposes  alone,  and  in  that  case,  part  of  the  air 
may  be  recirculated  to  save  refrigeration. 

♦Specification  for  safety  code  for  air-conditioning  (  revised  ). 
^Specification  for  safety  code  for  mechanical  refrigeration  (  revised ). 

13 


IS :  3103  - 1995 

4.3.5.2  The  proportion  of  recirculated  air  will  depend  on  the  circum- 
stances but  the  quantity  of  fresh  air  taken  in  shall  not  be  less  than  that  laid 
down  under  4.1  •2*1  or  that  required  as  make-up  air  to  replace  the  air 
exhausted  for  control  of  air  contaminants  {see  4.5)  whichever  is  higher. 

4.3.6  Fresh  air  shall  be  free  from  organic  matter  and  deleterious 
inorganic  dust  and  fume,  and  should  be  drawn  from  areas  where  the  air 
is  not  likely  to  be  polluted  or  vitiated;  where  necessary,  the  air  should  be 
efficiently  filtered. 

4.4  Air  Distribution  —  In  providing  ventilation,  proper  consideration 
should  be  given  to  size  and  distribution  of  windows  and  other  inlet  open- 
ings in  relation  to  outlet  openings  arrangement  of  ducts  and  selection  and 
disposition  of  fans  and  air  intake  grilles  so  as  to  give,  with  due  regard  to 
orientation,  prevailing  winds,  configuration  of  the  building  and  manufac- 
turing processes  carried  on,  maximum  possible  control  of  thermal  environ- 
ments in  the  work  rooms.  Air  should  be  distributed  evenly  without  dead 
air  pockets  or  undue  draughts  caused  by  high  inlet  velocities.  When 
ventilation  is  provided  by  infiltration  due  to  exhaust  of  air,  it  is  important 
that  windows  and  other  openings  near  the  fans  are  kept  closed  as  other- 
wise the  fans  would  draw  outside  air  from  these  openings  and  cause  what 
is  termed  'short  circuiting'. 

4.4.1  Air  Movement — The  rate  of  air  movement  in  the  vicinity  of 
workers  shall  be  such  as  to  give  reasonable  comfort  without  objectionable 
draughts.  In  general,  velocity  of  air  excess  of  60  m/min  should  be 
avoided  unless  the  temperatures  and  humidities  are  high. 

4.4.1*1  Where  heavy  manual  work  is  performed  by  workers,  a  greater 
degree  of  air  movement  may  be  desirable  depending  upon  the  tempera- 
ture and  humidity  of  air.  When  the  nature  of  the  manufacturing  pro- 
cesses demands  conditions  of  temperature  and  humidity  which  are  above 
the  normal  range  of  comfort,  the  question  of  rate  of  air  movement  requires 
critical  examination,  particularly  if  the  dry  bulb  temperature  is  above 
that  of  body.  If  the  air  is  capable  of  absorbing  heat  from  the  body  a 
blast  of  air  up  to  300  m/min  may  be  directed  at  the  workers  for  velocity 
cooling. 

4.5  Ventilation  for  Control  of  Air  Contaminants 

4.5.1  Local  Exhaust  Ventilation  —  When  in  a  work  room  by  reason  of 
manufacturing  processes  contaminants  are  given  off,  it  shall  be  necessary 
to  provide  an  efficient  local  exhaust  ventilation  of  the  points  at  which  the 
contaminants  are  released  to  reduce  their  concentration  in  the  working 
area  below  Threshold  Limit  Values  (TLV)  {see  0.4) .  Such  points  shall, 
as  far  as  possible,  be  enclosed,  but  if  it  is  necessary  to  have  an  access  while 
the  manufacturing  processes  are  carried  on,  the  exhaust  appliance  shall 

14 


IS:  3103 -1975 

confine  the  contaminants  as  much  as  possible  and  openings  for  access  shall 
be  located,  wherever  possible,  away  from  the  natural  path  of  the  contami- 
nants travel. 

4.5.1.1  When  an  exhaust  appliance  is  provided  to  enclose  the  point 
at  which  contaminants  are  released,  the  volume  of  air  required  is  cal- 
culated from  the  area  of  openings  and  the  capture  velocity  sufficient  to 
prevent  outward  escapement.  In  other  cases,  the  volume  of  air  required 
and  pattern  of  air  flow  in  front  of  the  exhaust  appliance  shall  be  such  that 
the  capture  velocities  necessary  to  overcome  air  currents  and  convey  the 
contacminants  by  causing  the  air  recommended  capture  velocities  arc 
listed  out  in  Table  3. 

TABLE  3    RANGE  OF  RECOMMENDED  CAPTURE  VELOCITIES 


Sl 
No. 

(1) 


ii) 


iii) 


iv) 


Condition  of  Dispersion 
OF  Contaminant 

(2) 


Released  with  practically  no 
velocity  into  quiet  air 

Released  at  low  velocity  into 
moderately  still  air 


Active  generation  into  zone 
if  rapid  air  motion 

Released  at  high  initial  velo- 
city into  zone  of  very  rapid 
air  motion 


EXAMFLBS 


(3) 


Capture  Velocity 


Evaporation  from  tanks 
degreasing  etc 

Spray    booths;   intermittent 
container  filling,  low 
speed   conveyor  transfers; 
welding;  plating;  pickling 

Spray  painting  in  shallow 
booths;  barrel  filling; 
conveyor  loading;  crushers 

Grinding:  abrasive  blasting, 
tumbling 


(4) 
m/s 
0-25-0-5 

0-5-10 


1-0-2 -5 


2*5-iO 


4*5*1 .2  The  sizes  of  the  ducts  shall  be  determined  considering  the 
volume  of  air  required  and  duct  velocities  necessary  to  convey  the  con- 
taminants with  minimum  possible  static  resistance  consistent  with  the 
economics  of  installation  and  operation.  Fan  shall  be  of  such  type  and 
size  as  to  move  the  required  volume  of  air  and  overcome  the  total  resis- 
tance of  the  local  exhaust  ventilation  system  including  the  air  cleaning 
devices. 

4*5*2  Dilution  Ventilation  —  Dilution  ventilation  is  employed  to  reduce 
the  concentration  of  contaminants  in  the  working  area  below  the  Thres- 
hold limit  Values  (TLV)  when  the  contaminants  are  of  low  toxicity  with 
TLV  above  100  ppm  (parts  per  million  by  volume)  and  the  quantity  of 
contaminants  generated  is  not  high  (such  as  vapours  given  off  by  organic 
solvents  of  low  toxicity).  However,  dilution  ventilation  is  not  as  satis- 
factory for  control  of  air  contaminants  as  is  local  exhaust  ventilation. 


15 


IS:  3103 -1975 

4«5«2*1  The  exhaust  outlets  and  the  air  supply  inlets  shall  be  so  located 
that  air  passes  through  the  zone  of  contamination  with  the  points  at  which 
the  contaminants  are  released  between  the  worker  and  the  exhaust  outlets. 
The  workers  should  not  stand  too  close  to  the  zone  where  contaminants 
are  released. 

4.5.2*2  If  the  rate  of  vapour  generation  of  rate  of  liquid  evaporation 
is  known,  the  dilution  air  requirements  is  calculated  from: 

Air  required  in  m^/kg  24  X   10«  X  A: 

of  evaporation        — 


molecular  weight  of  liquid  X  TLV 

where 

k  =  constant  varying  from  3  to  10  depending  on  solvent  in 
question,  uniformity  of  air  distribution,  dilution  of  vapours 
in  air,  location  of  exhaust  plant  and  its  proximity  to 
evolved  vapours,  and 

TLV  =  Threshold  Limit  Value  of  the  solvent 

4.5*3  Make^Up-Air — Sufficient  make-up-air  shall  be  brought  into  the 
work  room  by  natural  infiltration  or  by  positive  ventilation  at  suitable 
points  in  relation  to  the  exhaust  points  to  replace  the  air  exhausted  by 
local  exhaust  ventilation  or  by  dilution  ventilation,  and  the  air  may  be 
efficiently  filtered  or  treated,  when  necessary* 

5.  INSTALLATION  AND  OPERATION 

5.1  Location  —  Fans  and  other  equipment  may  be  located  in  convenient 
positions  considering  the  intake  of  fresh  air,  accessibility  for  maintenance 
and  noise  control. 

5»1.1  Where  the  exhaust  of  air  laden  with  inflammable  dusts,  gases  or 
vapours  is  conveyed  through  ducts,  the  electric  motor  and  fan  shall  be 
situated  outside  in  such  a  way  that  an  explosion  will  not  vent  into  the 
work  room.  The  fan  should  be  of  non-sparking  construction  and  the 
motor,  if  not  located  outside  the  air  stream,  should  be  of  flame  proof 
construction. 

5*2  I>ucts  —  Where  positive  ventilation  requires  ducts  for  proper  air 
distribution  considerable  advantage  may  be  achieved  by  incorporating  the 
ducts  into  the  building  structure  and  by  having  the  interior  surfaces  care- 
fully finished  to  render  them  smooth  and  air-tight  and  treated  to  prevent 
the  possibility  of  dust  being  scoured  from  the  walls  by  the  passing  air. 
For  removal  of  corrosive  or  dust  laden  contaminants,  ducts  shall  be  pro- 
tected against  corrosion  and  erosion  and  shall  be  installed  for  easy 
inspection,  maintenance,  repair  and  replacement, 

5.2.1  Where  metal  duct  work  is  installed,  it  shall  conform  to  IS  :  655- 
1963*. 


^Specification  for  metal  air  ducts  (  revised), 

16 


IS:  3103 -1975 

5.3  Noise  —  Where  in  a  work  room  owing  to  the  nature  of  manufacturing 
processes  carried  on,  noise  supression  is  important,  close  attention  shall  be 
given  to  the  design  and  installation  of  motors,  fans  and  ducts  to  ensure 
quite  operation  and  to  minimize  transmission  of  noise. 

5.4  The  performance  of  ventilating  equipment,  such  as  fans  and  filters, 
over  a  period  of  years  is  considerably  influenced  by  the  extent  of 
the  initial  provision  of  facilities  for  its  efficient  operation  and  maintenance. 
The  following  points  shall  be  borne  in  mind: 

a)  Adequate       access     for     inspection,     cleaning     and    repair     of 
component  parts; 

b)  Reasonable  space  during  operation; 

c)  Location    of    dampers    and    other  operating  controls  in  such   a 
position  as  would  permit  quick  and  easy  operation;  and 

d)  Adequate  lighting  and  ventilation  at  places  where  the  equipment 

is  to  be  operated  and  maintained. 

6.  TESTING 

6-1  All  parties  concerned  shall  agree  to  the  objects  of  test,  methods  and 
duration  of  test,  degree  of  accuracy  required  and  state  of  ventilating 
cquipm.ent  under  test.  The  plant  shoiild  be  run  during  norm.al  working 
hours  and  adjusted  properly  ]:rior  to  the  test. 

6*2  Amount  of  Air 

6.2.1  Positive  Ventilation  —  The  volume  of  outside  air  by  positive  ventila- 
tion shall  be  measured  by  appropriate  instruments,  such  as  a  properly 
calibrated,  'anemometer',  velocity* meter  and  pilot  tube.  To  measure  the 
average  velocity  of  £iir  flow,  it  is  ne^cessary  to  make  a  traverse  of  the 
instrument  over  the  cross*sectional  area  of  the  intake  openings  or  ducts 
and  obtain  the  average  velocity  from  these  results.  The  volume  of  air  is 
given  by: 

where 

Q^==  volume  of  air  in  m'/mirt, 

A  =  free  area  of  intake  openings  of  ducts  in  m^  and 

V  ~  average  velocity  of  air  in  m/min. 

6-2.2  Exhaust  of  Air — The  volume  of  exhaust  air  shali  be  measured  in 
the  same  manner  as  in  the  case  of  positive  ventilation  by  measurement  of 
air  Velocity  and  area  of  exhaust  ducts  or  openings,  and  multiplying  the 
one  with  the  other. 

17 


IS:  3103 -1975 

6.2.3  Natural  /filtration  —  This  is  difficult  to  measure  as  it  varies  from 
time  to  time.  The  amount  of  outside  air  by  natural  infiltration  through 
doors  or  windows  or  through  other  openings  depends  on  direction  and 
velocity  of  wind  outside  and/or  convection  effects  arising  from  temperature 
of  vapour  pressure  difference  (  or  both  )  between  inside  and  outside  of  the 
work  room. 

6.2.3.1  Ventilation  due  to  wind  outside  is  given  by  the  formula: 

d^EAV 
where 

Q^=  volume  of  air  in  m^niin; 

A  =  free  area  of  inlet  openings  in  m^; 

F—  velocity  of  wind  in  m/min;  and 

E  =  co-efficient  which  varies  from  0'5  to  0'6  whcit  openings  face 
wind,  and  0*25  to  0*35  when  openings  are  at  mi  angle. 

6«2.3.2  Ventilation  due  to  convection  effects  arising  from  tempera- 
ture difference  between  inside  and  outside  is  given  by: 

(1=.  TO  A^  h  {tr  -  to) 

where 

Q.  =  volume  of  air  in  m/min; 

A  =  free  area  of  inlet  openings  in  m^; 

h  =  vertical  distance  between  inlets  and  outlets  in  mm; 

tr=  average  temperature  of  indoor  air  at  the  outlet,  in  ^'C;  and 

to  =  temperatur-e  of  outdoor  air  in  °C. 

Note  —  The  equation  is  based  on  0*65  efFrctivenc^s   of  openings.    This  should  be 
reduced  to  0'50  if  conditions  are  not  favourable. 

6.2.3«3  When  areas  of  inlet  and  outlet  openings  are  unequal,  ^A'  given 
in  equations  under  6.2.3*1  and  6.2»3.2  will  be  the  smaller  area  and  the 
volume  of  air  will  be  increased  according  to  the  percentage  given  in  Fig.  1. 

6.2.3.4  Ventilation  by  combined  effect  of  wind  outside  and  tempera- 
ture difference  may  be  evaluated  as  follows: 

a)  Calculate  the  amount  of  outside  air  by  methods  given  under  6.2.3.1 
and  6.2.3.2, 

b)  Express  the  amount  of  air  due  to  method  6.2.3.2  as  a  percentage 
of  the  total,  and 

c)  Use  Fig,  2  to  determine  actual  fl6w  caused  by  the  combined  effect 
of  both. 

18 


is :  3103  •  1975 


40 

^MM 

■■ 

•- 

> 

y^ 

^ 

J 

/ 

Z    tn 

/ 

^ 

i 

^    in 

1 

^    " 

1 

L_ 

u 

t 

P"^ 

^ 

6 

Fig.  I 


ratio  of  outlet  to  inlet  or  vice -versa 

Increase  in  Flow  Caused  by  Excess  of  One 
Opening  Over  Another 


7 

§W   6 

IL  Z 

*t. 

tV 

gr 

!5$  -i 

L 

V 

\ 

^ 

H 

9S  ^ 

0 

1 

har 

J-3 

r 

h 

r 

4 

BT 

Ho 

Fig.   2 


FLOW  DUE  TO  TEMPERATURE 
CNFFEREtK  AS  PERCENT  OF  TOTAL 

Determination  of  Flow  Caused  by  Combined  Forces  of 
Wind  and  Temperature  Difference 


6.2.4  Combined  Effect  of  Different  Methods  of  Ventilation  —  When  combina- 
tion of  two  or  more  methods  of  general  ventilation  is  used,  the  total  rate  of 
ventilation  shall  be  reckoned  ?s  the  highest  of  the  following  three: 

a)  rate  of  positive  ventilation  {see  6.2.1  ), 

b)  rate  of  exhaust  air  (  see  6*2«2  ),  and 

c)  1*25  times  the  rate  of  natural  infiltration  (  see  6.2.3  ). 

This   rule  shall    be  followed  until  an   exact  formula  is   established 
by  research. 

19 


IS:  3103- 1975 

6.3  Air  Movement  —  Turbulent  air  movement  at  the  working  zone  may 
be  measured  either  by  Kata  thermometer  (dry  silvered  type),  heated 
thermo  anemometer  or  properly  calibrated  thermocouple  anemometer. 
Kata  thermometer  and  heated  thermometer  give  cooling,  power  rather 
than  the  velocity  of  air,  and  the  rate  of  air  movement  is  found  out 
from  the  cooling  power  by  reference  to  a  nomogram  using  the  ambient 
temperature. 

6.4  Tolerances  —  The  rate  of  air  flow  as  measured  in  the  duct  or  at  a 
grille  either  by  positive  ventilation  or  exhaust  of  air  shall  be  within 
10  percent  of  the  amount  required. 

6.4.1  Variation  of  air  flow  through  filters  and  grilles  shall  not  at  any 
time  be  more  than  db  20  percent  of  the  mean  value. 

7.  MAINTENANCE 

7.1  All  ventilating  equipment  shall  be  checked  periodically  and  bearings 
of  various  moving  parts  lubricated.  The  equipment  shall  also  be  tested 
for  air  delivery.     Such  tests  shall  be  made  at  least  once  in  a  year. 

7.2  The  surfaces  of  any  cooling  or  heating  units  and  air  cleaning  devices 
(  including  filters )  shall  be  inspected  at  frequent  intervals  for  corrosion 
and  dirt  and  when  corrosion  occurs  the  corroded  parts  shall  be  carefully 
cleaned  and  protected  with  anti-corrosion  paint  or  other  suitable  medium. 
Cleaning  of  filters  and  heat  transfer  units  shall  be  carried  put  regularly  to 
promote  their  efficient  use. 

8.  SAFETY  REQjUIREMENTS  FOR  ELECTRICAL  EQUIPMENT 

8.1  Electrical  Equipment — Electrical  wiring  and  installation  of  electrical 
equipment  shall  be  in  accordance  with  the  requirements  of  Indian  Electri- 
city Act  f*nd  Rules  and  shall  also  conform  to  IS  :  732-1963*  arid 
IS  :  2274-19631  as  applicable. 

8.2  Fire  Safety  —  Due  consideration  shall  be  given  to  the*  fire  safety 
aspects  as  given  in  IS  :  1646-1961  J. 


•Code  of  practice  for   electrical  wiriiig   iflstaUations   (system  voltage  not  exceeding 
650  volts  )  (  revised  ) . 
fCode  of  practice   for  electrical  wiring  installationi     (system   voltage    exceeding 
650  volts). 
JCode  of  pi^ctice  for  fire  safety  of  buildings  (general  )  electrical  installations. 

20 


BUREAU  OF  INDIAN  STANDARDS 


Headquarters  : 

Mana|cJ|havan,  9  Bahadur  Shah  Zafar  Marg,  NEW  DELH1 110002 
Telephones  :  331  01  31  Telegrams  :  i 

33113  75  (Common 

Regionai  Offices  : 

Central  ;  Manak  Bhavan,  9,  Bahadur  Shah  Zafar  Marg. 

NEW  DELH II 10002 
•Eastern         :  1/14  C.I.T.  Scheme  VII  M, 

V.I.P.  Road,  Maniktola,  CALCUTTA  700054 
Northern       :  SCO  445-446,  Sector  35-C,  CHANDIGARH  160036 
Southern      :  C.l.t.  Campus,  IV  Cross  Road,  MADRAS  600113 
t  Western        :  Manakalaya,  E9  Ml  DC,  MaroL  Andheri  (East), 
BOMBAY  400093 
Brancfi  Offices  : 

'Pushpak',  Nurmohamed  Shaikh  Marg,  Khanpur,  AH MADABAD  380001 
t  Peehya  Industrial  Area,  1st  Stage,  Bangalore-Tumkur  Road, 

BANGALORE  560058  _^ 

Gangotrl  Complex,  5th  Floor,  Bhadbhada  Road,  T.T.  Nagar, 

BHOPAL  462003 
Plot  No.  82/83,  Lewis  Road,  BHUBANESHWAR  751002 
Kalai  Kathir  Building,  6/48-A  Avanasi  Road,  COIMBATORE  641037 
Quality  Marking  Centre,  N-H.  IV,  N-LT.,  FARIDABAD  121001 
Savitri  Complex,  116  G.T.  Road,  GHAZIABAD  201001 
53/5  Ward  No.  29,  R.G.  Barua  Road,  5th  By-lane, 

GUWAHATI  781003  / 

5-8-56C  L.  N.  Gupta  Marg,  (  Nampally  Station  Road  ) 

HYDERABAD  500001 
R14  Yudhister  Marg,  C  Scheme,  JAIPUR  302005 
117/418  B  Sarvodaya  Nagar,  KANPUR  208005 

Plot  No.  A-9,  House  No.  561/63.  Sindhu  Nagar,  Kanpur  RoaO, 
LUCKNOW  226005 

Pattiputra  Industrial  Estate,  PATNA  800013 

District  Industries  Centre  Complex,  Bagh-e-AII  Maidan, 
SRI  NAGAR  190011 

T.  C.  No.  14/1421,  University  P.O.,  Palayam. 

THIRUVANANTHAPURAM  695034 
inspection  Offices  (With  Sale  Point)  : 
Pushpanjali.  First  Floor,  205'A  W^t  High  Court  Road. 

Shankar  Nagar  Square,  NAGPUR  440010 
Institution  of  Engineers  (India)  Building,  1332  Shivaii  Nagar. 

PUNE  411005 


Manaksanstha 

to  all  Offices) 

Teiepfione 

J  331  0131 

Z331  13  75 

37  86  62 

218  43 

41  2916 

6  32  92  95 

1           2  63  48 
39  49  55 

55  40  21 

5  36  27 
2  67  05 

8-71  19  96 
3  31  77 

2310  83 

6  34  71 
21  68  76 

5  55  07 

•Sales  Office  Calcutta  is  at  5  Chowringhee  Approach, 
P.  O.  Princep  Street,  CALCUTTA 

t    Sales  Office  is  at  Novelty  Chambers.  Grant  Road,  BOMBAY 

%  Sales  Office  is  at  Unity  Building,  Narasimharaja  Square, 
BANGALORE 


6  23  05 

6  21  04 

62  51  71 
6  24  35 

27  68  00 

89  66  28 
22  39  71 


Reprography  Unit,   BIS,  New  Delhi,   India